VentilationAlarm EP2 / ES 1162 is a universal alarm with sound and light signal.
EP2 has a connection for backup battery, input for 0-10V signal and temperature measurement, relay output and pressure sensor for control of ventilation system, local extraction etc. The EP2 is equipped with a green operation LED, red alarm LEDs and a mute button. (Muting the sound does not affect the visual alarm).
EP2 can function as:
– Pressure monitor (monitored via the built-in pressure sensor).
– Signal guard (0-10V signal from an external sensor, e.g. flow or humidity sensor).
– Temperature monitor (External NTC sensor is connected).
Factory setting is Pressure monitoring.
EP2 is also equipped with a relay output which can e.g. drive a secondary alarm lamp.
EAN-Number | 5703471491470 |
---|---|
Size (HxWxD) | 122x120x56 mm |
Enclosure | IP 53 |
Supply Voltage | 100 - 240 VAC |
Frequency | 50 Hz |
Power outlet | 24 VDC |
Ambient temperature | 0 - 50 °C |
Sensor Type | Tryktransducer |
Measurement Area | 9 - 2500 Pa |
Relay Output | 8A AC1 |
0-10V Input Impedance | 10 mA |
Sound Level | >85 dBA @ 10cm |
Communication interface | MODBUS |