PressureTransducer 0-25Pa with 0-10V DC output signal based on micro-flow measurement.
The pressure transducer is equipped with a half/full scale selector. Use the jumper to switch between half scale and full scale. In half scale mode, the output voltage is 10 volt at 50% of the sensors maximum. Example: In half scale mode the pressure transducer has an output of 0V at 0Pa and 10V at 12,5 Pa. If the unit in half scale mode is exposed to a pressure outside the max range, the output voltage may increase to 12V.
NB! The pressure transducer is only to be used in a non condensing environment and in non aggressive air.
This product is being discontinued, only 4 left.
No direct substitution for this pressure area. However, in most casses PressureBox ED 50 / ES 1088 (item number 4075) can be used.
EAN-Number | 5703471407440 |
---|---|
Size (HxWxD) | 80x80x55 mm |
Enclosure | IP 54 |
Supply Voltage | 24 VAC |
Alternate Supply | 15 - 30 VDC |
Ambient temperature | -20 - 60 °C |
Measure Area | 0-25 Pa |
Measure Area 2 | 0 - 12.5 Pa |
Number of 0-10V Outputs | 1 |
0-10V Output Current | 10 mA |
“If you have any questions or need assistance choosing from or using our products, you are welcome to contact customer service:”
Since 1969, we have supplied electronics for management, regulation and control to quality-conscious companies
Receive our newsletter about 4 times a year with information about what is happening with us and in the market.
LS Control A/S | Copyright © 2022 All rights reserved.