VentilationAlarm EP2 24V / ES 1162

Item no.: 49148

View dealers
Support If you have questions or need assistance in choosing amongst or using our products, please do not hesitate to contact customer service:

VentilationAlarm EP2 / ES 1162 is a universal alarm with sound and light signal.

EP2 has a connection for backup battery, input for 0-10V signal and temperature measurement, relay output and pressure sensor for control of ventilation system, local extraction etc. The EP2 is equipped with a green operation LED, red alarm LEDs and a mute button. (Muting the sound does not affect the visual alarm).

EP2 can function as:
– Pressure monitor (monitored via the built-in pressure sensor).
– Signal guard (0-10V signal from an external sensor, e.g. flow or humidity sensor).
– Temperature monitor (External NTC sensor is connected).

Factory setting is Pressure Monitoring.

EP2 is also equipped with a relay output which can e.g. drive a secondary alarm lamp.

Sound Level

>85 dBA @ 10cm

Measurement Area

9 – 2500 Pa

0-10V Input Impedance

10 mA

Communication interface

MODBUS

Ambient Operating Temperature

0 – 50 °C

Power outlet

24 VDC

Enclosure

IP 53

Frequency

50 Hz

Alternate Supply

24 VDC

Relay Output

8A AC1

Size (HxWxD)

122x120x56 mm

Sensor Type

Tryktransducer

Supply Voltage

24 VAC

EAN Number

5703471491487

Product Sheet VentilationAlarm EP2 24V / ES 1162 Manual for VentilationAlarm EP2 / ES 1162 Drawing Showing Correct Placement of Tube Fitting