Product is discontinued.
No direct substitution for this pressure area. However, in most casses PressureBox ED 50 / ES 1088 (item number 4075) can be used.
PressureTransducer 0-25Pa with 0-10V DC output signal based on micro-flow measurement.
The pressure transducer is equipped with a half/full scale selector. Use the jumper to switch between half scale and full scale. In half scale mode, the output voltage is 10 volt at 50% of the sensors maximum. Example: In half scale mode the pressure transducer has an output of 0V at 0Pa and 10V at 12,5 Pa. If the unit in half scale mode is exposed to a pressure outside the max range, the output voltage may increase to 12V.
NB! The pressure transducer is only to be used in a non condensing environment and in non aggressive air.