Bundle with constant pressure regulator ES 10 and PressureBox E 2500 / ES 1088, incl. 2m silicone tube and metal tube fitting.
Constant pressure regulator ES 10 is designed for use in ventilation plants. ES 10 is equipped with a 0-10V DC output and an on/off relay for control of an inverter or triac controller.
The ES 10 has 3 diferent operating modes; day, night and maximum opreation.
Furthermore a temperature sensor can be connected for outdoor temperature compensation.
The voltage free contact makes it possible to connect the ES 10 to the BMS system or other type of alarm system.
PressureBox E2500 / ES 1088 is in this configuration functioning as pressure transducer and has a selection of 4 different pressure areas, in order 0-250Pa, 0-500Pa, 0-1500Pa and 0-2500Pa. Factory setting is 0-500Pa.
Enclosure | IP 54 |
---|---|
Supply Voltage | 230 VAC |
Frequency | 50 Hz |
Max. tolerance of supply | 10% |
Ambient temperature | 0 - 50 °C |
Sensor Type | Tryktransducer |
Precision Sensor | 1,5% af målt værdi (3Pa) |
Measurement Area | 0 - 2500 Pa |
0-10V Output Current | 20 mA |