PressureTransducer 250Pa/ ES 961 – under discontinuance

Item no.: 40742

View dealers

Support

If you have questions or need assistance in choosing amongst or using our products, please do not hesitate to contact customer service:

Pressure transducer 0-250 Pa with 0-10V DC output signal based on micro-flow measurement. The pressure transducer is eqquipen with a half/full scale selector. Use the jumper to switch between half scale and full scale. In half scale mode, the output voltage is 10V at 50% of the sensors maximum.

Eg. In half scale mode the pressure transducer has an output of 0V at 0 Pa and 10V at 125 Pa. If the unit in half scale mode is exposed to a pressure exceeding the max range, the output voltage may increase to 12V.

NB !! The pressure transducer is only to be used in non condensing environment and in non aggressive air.

This product is being discontinued. Approx. 40 pcs. left.

 

EAN Number

5703471407426

Size (HxWxD)

80x80x55 mm

Enclosure

IP 54

Supply Voltage

24 VAC

Alternate Supply

15 – 30 VDC

Ambient Operating Temperature

-20 – 60 °C

0-10V Output Current

10 mA

Measurement Area

0 – 250 Pa

Measurement Area 2

0 – 125 Pa

Guide for Pressure Transducer / ES 961
Declaration of Conformity (Danish only)